| ======Auto Mains Fail Transfer Switch :: ComAp Inteli-ATS==== | ======Auto Mains Fail Transfer Switch :: ComAp Inteli-ATS==== | ||
| - | {{ : | + | {{ ::zref: |
| This automatic transfer switch uses a [[https:// | This automatic transfer switch uses a [[https:// | ||
| * [[https:// | * [[https:// | ||
| Line 8: | Line 8: | ||
| The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https:// | The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https:// | ||
| - | * //See the discussion at [[ats: | + | * //See the discussion at [[:zref:ats:start# |
| + | |||
| + | ---- | ||
| + | \\ | ||
| + | <WRAP center round alert 60%> | ||
| + | \\ | ||
| + | **See warnings below** | ||
| + | </ | ||
| + | \\ | ||
| + | ---- | ||
| =====One-Line Diagram=== | =====One-Line Diagram=== | ||
| - | {{: | + | {{::zref:ats:e117.1_r1.1_auto_transfer_switch_inteliats.png? |
| ===Auto Mains Fail Transfer Switch== | ===Auto Mains Fail Transfer Switch== | ||
| <WRAP col2> | <WRAP col2> | ||
| - | | + | One-line diagram, detailed schematic/ |
| - | * {{ : | + | |
| + | * {{ ::zref: | ||
| + | \\ | ||
| + | //(DSN) files can be edited with [[https:// | ||
| </ | </ | ||
| - | //(DSN) files can be edited with [[: | ||
| - | |||
| =====Description of Operation=== | =====Description of Operation=== | ||
| Contactors K-U [3] and K-G [5] are mechanically and electrically interlocked to ensure that only one can be closed at a time. | Contactors K-U [3] and K-G [5] are mechanically and electrically interlocked to ensure that only one can be closed at a time. | ||
| Line 42: | Line 51: | ||
| - If utility power fails to return within 5 seconds: | - If utility power fails to return within 5 seconds: | ||
| - InteliATS closes KGS [6] to start the genset | - InteliATS closes KGS [6] to start the genset | ||
| - | - Once the generator is running, the InteliATS: | + | - Once the generator is running, the Inteli: |
| - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | ||
| - Illuminates L-G (Blue) indicating generator power is OK. | - Illuminates L-G (Blue) indicating generator power is OK. | ||
| Line 52: | Line 61: | ||
| ====Utility Power Return== | ====Utility Power Return== | ||
| - | - When Utility Power returns, | + | - When Utility Power returns, |
| - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | ||
| - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable | - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable | ||
| Line 84: | Line 93: | ||
| =====Bill of Materials== | =====Bill of Materials== | ||
| + | **// | ||
| ====117 ATS -- Automatic Transfer Switch-Contactor=== | ====117 ATS -- Automatic Transfer Switch-Contactor=== | ||
| * [[https:// | * [[https:// | ||
| Line 93: | Line 102: | ||
| < | < | ||
| + | {{page>: | ||
| + | |||
| + | <WRAP center round alert 80%> | ||
| + | **DANGER:** Current transformers must be connected to a device, or short-circuited before power is applied in the circuit to be measured. Current transformers are //constant current// devices, not //constant voltage// like ordinary transformers. | ||
| + | |||
| + | * **A C.T. with loose leads can have lethal voltage on the terminal, possibly over 1000V.** | ||
| + | |||
| + | * **Do not disconnect a C.T. when power is present in the measured circuit!** | ||
| + | </ | ||