 ======Auto Mains Fail Transfer Switch :: ComAp Inteli-ATS==== ======Auto Mains Fail Transfer Switch :: ComAp Inteli-ATS====
-{{ :ats:inteliats2_70_main.jpg?direct&300|}}+{{ ::zref:ats:inteliats2_70_main.jpg?direct&300|}}
 This automatic transfer switch uses a [[https://www.comap-control.com/products/switchgear-control-and-protections/ats-controllers/|ComAp ATS Controller]] combined with motor contactor switching to provide a fully-featured ATS with full metering & history logging, and can also be remotely monitored.  This automatic transfer switch uses a [[https://www.comap-control.com/products/switchgear-control-and-protections/ats-controllers/|ComAp ATS Controller]] combined with motor contactor switching to provide a fully-featured ATS with full metering & history logging, and can also be remotely monitored. 
   * [[https://www.comap-control.com/products/switchgear-control-and-protections/ats-controllers/inteliats2-50/|InteliATS 50]]    * [[https://www.comap-control.com/products/switchgear-control-and-protections/ats-controllers/inteliats2-50/|InteliATS 50]] 
Line 8: Line 8:
 The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https://www.factorymation.com/Contactors_Overloads_qs/Metasol-Contactors-Overloads-9-to-800A?Coil_Voltage=240V-AC-Class&Nominal_Amps=150,225,400,800|FactoryMation.com]] //(225A frame and larger have 100-240VAC/DC coils)//  The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https://www.factorymation.com/Contactors_Overloads_qs/Metasol-Contactors-Overloads-9-to-800A?Coil_Voltage=240V-AC-Class&Nominal_Amps=150,225,400,800|FactoryMation.com]] //(225A frame and larger have 100-240VAC/DC coils)// 
  
-  * //See the discussion at [[ats:start|ATS Pro & Con]] for reasons why this may or may not be an appropriate choice for your application.// +  * //See the discussion at [[:zref:ats:start#contactor-based-atspro-con|ATS Pro & Con]] for reasons why this may or may not be an appropriate choice for your application.//  
 + 
 +----  
 +\\  
 +<WRAP center round alert 60%> 
 +\\  
 +**See warnings below**  
 +</WRAP> 
 +\\  
 +---- 
  
  
 =====One-Line Diagram=== =====One-Line Diagram===
-{{:ats:e117.1_r1_auto_transfer_switch_inteliats.png?direct&600 |}}+{{::zref:ats:e117.1_r1.1_auto_transfer_switch_inteliats.png?direct&600 |}}
  
 ===Auto Mains Fail Transfer Switch== ===Auto Mains Fail Transfer Switch==
 <WRAP col2> <WRAP col2>
-  * {{ :ats:e117.1-3_r1_auto_transfer_switch_inteliats.pdf |}} +One-line diagram, detailed schematic/wiring diagram, and parts list: 
-  * {{ :ats:e117.1-3_r1_auto_transfer_switch_inteliats.dsn |}} +  * {{ ::zref:ats:e117.1-3_r1.1_auto_transfer_switch_inteliats.pdf |}} 
 +  * {{ ::zref:ats:e117.1-3_r1.1_auto_transfer_switch_inteliats.dsn |}} 
 +\\  
 +//(DSN) files can be edited with [[https://www.metatek.org/tinycad|TinyCAD]].//
 </WRAP> </WRAP>
-//(DSN) files can be edited with [[:TinyCAD|]].// 
- 
 =====Description of Operation=== =====Description of Operation===
 Contactors K-U [3] and K-G [5] are mechanically and electrically interlocked to ensure that only one can be closed at a time.  Contactors K-U [3] and K-G [5] are mechanically and electrically interlocked to ensure that only one can be closed at a time. 
Line 42: Line 51:
   - If utility power fails to return within 5 seconds:    - If utility power fails to return within 5 seconds: 
     - InteliATS closes KGS [6] to start the genset     - InteliATS closes KGS [6] to start the genset
-  - Once the generator is running, the InteliATS+  - Once the generator is running, the Inteli:zref:ats
     - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency     - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency
     - Illuminates L-G (Blue) indicating generator power is OK.     - Illuminates L-G (Blue) indicating generator power is OK.
Line 52: Line 61:
  
 ====Utility Power Return== ====Utility Power Return==
-  - When Utility Power returns, InteliATS+  - When Utility Power returns, Inteli:zref:ats
     - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency     - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency
     - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable     - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable
Line 84: Line 93:
  
 =====Bill of Materials== =====Bill of Materials==
 +**//[Incomplete, work in progress]//**
 ====117 ATS -- Automatic Transfer Switch-Contactor=== ====117 ATS -- Automatic Transfer Switch-Contactor===
   * [[https://docs.google.com/spreadsheets/d/1r8JlMTjobZA3-YeLz29EerO8OxSNKXO5SXB6vngvN9Y/edit?usp=sharing|BOM 117 -- Google Sheets]]   * [[https://docs.google.com/spreadsheets/d/1r8JlMTjobZA3-YeLz29EerO8OxSNKXO5SXB6vngvN9Y/edit?usp=sharing|BOM 117 -- Google Sheets]]
Line 93: Line 102:
 <html><iframe width="950px" height="600px" src="https://docs.google.com/spreadsheets/d/e/2PACX-1vTpnSXQxSW-pyEPUDI_RqkSWwlRZ5bm6xUZVdUwxoYJp45-My7mLLED89SG-gxo4DX0bJ0KjPFYXsjP/pubhtml?gid=0&amp;single=true&amp;widget=true&amp;headers=false"></iframe></html> <html><iframe width="950px" height="600px" src="https://docs.google.com/spreadsheets/d/e/2PACX-1vTpnSXQxSW-pyEPUDI_RqkSWwlRZ5bm6xUZVdUwxoYJp45-My7mLLED89SG-gxo4DX0bJ0KjPFYXsjP/pubhtml?gid=0&amp;single=true&amp;widget=true&amp;headers=false"></iframe></html>
  
 +{{page>:warnings&nofooter}}
 +
 +<WRAP center round alert 80%>
 +**DANGER:** Current transformers must be connected to a device, or short-circuited before power is applied in the circuit to be measured. Current transformers are //constant current// devices, not //constant voltage// like ordinary transformers. 
 +
 +  * **A C.T. with loose leads can have lethal voltage on the terminal, possibly over 1000V.** 
 +
 +  * **Do not disconnect a C.T. when power is present in the measured circuit!** 
 +</WRAP>
  