| - If utility power fails to return within 5 seconds: | - If utility power fails to return within 5 seconds: | ||
| - InteliATS closes KGS [6] to start the genset | - InteliATS closes KGS [6] to start the genset | ||
| - | - Once the generator is running, the Inteli: | + | - Once the generator is running, the InteliATS |
| - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | ||
| - Illuminates L-G (Blue) indicating generator power is OK. | - Illuminates L-G (Blue) indicating generator power is OK. | ||
| Line 61: | Line 61: | ||
| ====Utility Power Return== | ====Utility Power Return== | ||
| - | - When Utility Power returns, | + | - When Utility Power returns, |
| - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | - Qualifies input for minimum, maximum voltage on all phases, correct phase rotation, minimum, maximum frequency | ||
| - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable | - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable | ||